Chapter 10 (cont..1) - Deflection control and preliminary dimensions of flanged beams

In the previous section, we have seen the conditions for ensuring integral action between the slab and the beam. We also saw different types of flanged beams and their performances. Now we will see the basic requirements that a newly designed 'flanged beam' should satisfy.

The basic concepts of the process of design of singly reinforced rectangular sections were discussed earlier. There, in the introduction part, we discussed about:
1.concrete cover 
2.Minimum distance to be provided between the bars of beams
3.Maximum spacing allowable between bars of beams
4.Beams with overall depth greater than 750 mm
5.Minimum area of flexural reinforcements in beams
6.Maximum allowable area of flexural reinforcements in beams
7.Deflection control of singly reinforced beams and
8.Guide lines for fixing up the dimensions of beams


Links to each of the above items can be seen here.

All the above eight topics are applicable to Flanged beams also. However, some minor modifications have to be made to some of them. We will now look at the required modifications:


No.5: Minimum area of flexural reinforcements in flanged beams

We have seen that the minimum area of flexural reinforcement required in the case of a rectangular section is given by Eq.4.1

In the case of flanged sections, the width b should be replaced by bw, the width of the web. So we get

Eq.10.1


No.6: Maximum allowable area of flexural reinforcements in flanged beams


Similar to the above,  the width b should be replaced by bw, the width of the web. So we get

10.2
Ast  0.04bwD 


No.7: Deflection control of singly reinforced flanged beams


We have seen the modification factors that have to be applied to the basic l/d ratio. There we mentioned that the reduction factor kf will be discussed when we take up the design of flanged sections. In fact, we have to do two things: 
• we have to see some modifications to the factor kt and 
• we have to learn about the new factor kf

So we now look at cl 23.2.1(e) of the code. When we do the deflection calculations for a singly reinforced 'flanged beam', we have to determine the values of three quantities: Modification factor α, Modification factor kt, and the reduction factor  kf. The final equation can be written as:

(l/d)actual  ≤  [(l/d)basicα kt kf 

Modification factor α can be determined by the same procedure as for a rectangular section. It may be noted that we do not need to calculate α if the span is less than 10 m, because then it's value is equal to 1.

Let us first see kt: To calculate kt, we have to first calculate the percentage of tension reinforcement by using the equation:


Where Ast,p is the actual area of steel provided

But in our present case of flanged beams , the effective width of flange, bf has to be used instead of b . So the equation becomes:

The rest of the procedure for calculating kt  is same as that for a rectangular beam.

Now we come to the factor  kf.  For it's calculation, first we calculate the ratio of 'web width' to 'flange width'. That is, the ratio: bbf  . Then we use this ratio to obtain kf from the fig 6 of the code.

Thus we can write the deflection control equations in the final form:

10.3
For singly reinforced flanged beams with span less than 10m,

(l/d)actual  ≤  [(l/d)basickkf

10.4
For singly reinforced flanged beams with span greater than 10m,

(l/d)actual  ≤  [(l/d)basicα kkf

If the beam is a cantilever with span greater than 10 m, actual deflection calculations should be made.

So we have Seen the code procedure for deflection control of a flanged beam. But this method has been found to give results that are not normally expected. So it is recommended that for calculations regarding deflection control of a flanged beam, the over hanging portions should be ignored, and it should be considered as a rectangular section of width bw and effective depth d . That is., when we have to do the deflection control calculations of a singly reinforced flanged section, we must consider it as a rectangular section of width bw, and effective depth d, and then do the calculations.


No.8: Guide lines for fixing up the dimensions of beams


Fig.10.11 below shows the view of a part of a structure. It shows a slab supported over some beams and masonry walls. If the slab is cast integrally with the beams, and the condition of the arrangement of slab bars mentioned in the previous section is satisfied, they can be considered as T-beams. As these T-beams are supported over a number of masonry walls, they are 'continuous T-beams.'

Fig.10.7
3D View of Continuous T-beams
In continuous beams, bending moments at supports will be generally greater than the bending moments at other portions.

Let us consider any one of these continuous T-beams. We can analyse it and draw a bending moment diagram. Fig 10.8 below shows a portion of a typical bending moment diagram of a continuous system. It is shown here to get an understanding about the 'nature of bending moments' in continuous systems. And also to see a comparison between the 'values' of the bending moments. A video about continuous systems can be seen here.  

Fig.10.8
Portion of a Bending moment diagram
Bending moments at supports greater than the bending moments at midspans

We can see that at the continuous supports, the Bending moment has values of 19.3 and 18. But at mid span, it has a lower value of 12.9. In this way, the bending moment at continuous supports will normally be higher than the bending moments at mid spans. So the higher bending moments at these supports should be used to fix up the dimensions of the beams.

However, each structure should be examined and analysed carefully to see if this general rule is true for that structure.

It should also be noted that the bending moment at supports are hogging moments. So the beam will experience tension at the fibres above the neutral axis. So the flange, which is at the top portion of the beam will be under tension, and the concrete in the flange will have cracked. So the flange cannot be considered in the design. Thus, at the supports, the beam section should be designed as a rectangular section. Towards the midspan, the moment becomes sagging type. Here the beam will act as a proper flanged beam. But the width of the web bw and effective depth d are already fixed by considering the moments at the supports. So the only calculation to be done here is that of the tension steel. But the effective width bf of the flange has to be calculated prior to the calculation of steel. So in the case of continuous T-beams, the preliminary dimensions are fixed by the methods that we discussed for 'rectangular sections'. And these methods should be applied at the supports. We can say that there are no new methods to be learnt for fixing up the preliminary dimensions of a 'continuous T-beam'.

But this is not the case of 'simply supported T-beams'. Here we do have to learn some new methods. Especially for fixing up the 'preliminary depth'. Fig.10.13 below shows the view of some simply supported T-beams. (The slab above the beams is not shown in the fig. for clarity)

Fig.10.13
3D view of Simply supported T-beams
Analysis and design of simply supported flanged beams having T or L section

In this case, the bending moment at supports is equal to zero. Towards the mid span, there will be sagging moment in the beam, and the flange will take up compressive force. So it will act as a proper T-beam. The traditional method for fixing up the preliminary width is same as that for a rectangular section.  We saw those details here. Based on that discussion, bw is selected from general values such as  200, 230, 250, 300 etc.,

Now we come to the depth. We have earlier seen (in the discussion on rectangular beams) that, the strength (to resist bending) of a beam can be increased by increasing  either it's depth or width. So a beam having a large width will have considerable strength. A T-beam or L-beam will indeed be having a larger width, on account of their flange. This will mean that these beams can withstand the bending moments even if they have smaller depths. But in reality, we must not provide smaller depths under any circumstances. This is because, the increased strength obtained from the increased width may be sufficient to resist bending. But the increased strength obtained in this way will not help the beam to resist 'Shear'. Also it will not help the beam to 'control deflection'. That is., even if smaller depth is sufficient to resist 'bending', we do have to provide sufficient depth to resist other effects like 'shear', 'torsion' etc., Also sufficient depth is required to control 'deflection'. 

So the method that we will use to fix up the preliminary depth should take into account the above points. The range of 13 to 16 for l/D ratio, gives satisfactory results for flanged sections. From the value of D, we usually deduct 50 mm to obtain d. We know that the quantity of '50 mm' is obtained by simple calculations on some assumed values: [Concrete cover 30 mm] + [dia. of links 10 mm] + [half the dia. of main bars = half of 20 = 10 mm] = 50 mm. Here the main bars of 20 mm dia. are assumed to be placed in a single layer. But when heavy loads are acting, a large quantity of bars will have to be provided. Such large quantities can be accomodated only if we arrange the bars in 'layers'.

When the bars are arranged in layers, the above quantity of '50 mm' will change significantly. Consider the scenario:
• We start off by simply deducting 50 mm
• The beam actually have a much different 'd' from that calculated using 50 mm
Then the subsequent calculations will not give correct results. This is particularly important for flanged beams because, as we will soon see, there are a lot of calculations involving 'd'. So it is important to get a fairly good approximation of 'd' in the initial stage itself. In the next section we will see how this can be done.